General
The MS-5UD-3(E) is a five-zone FACP (Fire Alarm ControlPanel) and the MS-10UD-7(E) is a ten-zone FACP. These controlpanels provide reliable fire signaling protection for small tomedium-sized commercial, industrial, and institutional buildings.Both panels include built-in communicators for CentralStation Service and remote upload/download.Each of these FACPs is compatible with System Sensor’smicroprocessor-based i3 series detectors. These conventionalsmoke detectors can transmit a maintenance trouble signal tothe FACP indicating the need for cleaning and a supervisory “freeze” signal when the ambient temperature falls below the detector rating. Additionally, both the MS-5UD-3 and MS-10UD-7 are compatible with conventional input devices such as two- and four-wire smoke detectors, pull stations, waterflow devices, tamper switches, and other normally-open contact devices. Refer to the Fire•Lite Device Compatibility Document for a complete listing of compatible devices. Outputs include four NACs (Notification Appliance Circuits),three programmable Form-C relays (factory programmed for Alarm, Trouble, and Supervisory) and 24 VDC special application resettable and nonresettable power outputs. The FACPs supervise all wiring, AC voltage, battery level and telephone line integrity. Activation of a compatible smoke detector or any normallyopen firealarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, sound the
piezo sounder at the FACP, activate the communicator and FACP alarm relay, and operate an optional module used to notify a remote station or initiate an auxiliary control function. New options include a UL listed printer, PRN-6F and FireLite’s IPDACT Internet Monitoring module. The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet saving the monthly cost of two telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. NOTE: The MS-5UD-3E and MS-10UD-7E offers the same features as the MS-5UD-3 and MS-10UD-7 but allow connection to 240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 120 VAC and the 240 VAC versions of these panels. NOTE: For ULC-listed models, see DF-60440.
Features
• Listed to UL Standard 864, 9th edition.
• Built-in DACT (Digital Alarm Communicator/Transmitter).
• Style B (Class B) IDC (Initiating Device Circuit)
– MS-5UD-3 - five IDCs.
– MS-10UD-7 - ten IDCs.
• Style Y (Class B) NAC (Notification Appliance Circuit) - special
application power
– MS-5UD-3 - four NACs.
– MS-10UD-7 - four NACs.
• Notification Appliances may be programmed as
– Silence Inhibit.
– Auto-Silence.
– Strobe Synchronization for System Sensor, Wheelock,
Gentex, Faraday, or Amseco devices.
– Selective Silence (horn-strobe mute).
– Temporal or Steady Signal.
– Silenceable or Nonsilenceable.
• Optional CAC-5X Style Z (Class A) Converter Module for
NACs and IDCs (2 required for MS-10UD-7).
• Form-C Relays for Alarm, Trouble and Supervisory - Contact
Ratings 2.0 A@ 30 VDC or 0.5 A @ 30 VAC (resistive).
• 3.0 A total system current for MS-5UD-3.
• 7.0 A total system current for MS-10UD-7.
• Optional Dress Panel DP-51050
• Optional Trim Ring TR-CE for semi-flush mounting.
• 24 volt operation.
• Low AC voltage sense.
• Alarm Verification.
• PAS (Positive Alarm Sequence).
• Automatic battery trickle charger.
• Up to eight ANN-BUS annunciators:
– Optional 8 zone Relay Module ANN-RLY.
– Optional LED Annunciator Module ANN-LED,
– Optional Remote Annunciator ANN-80.
– Optional Remote Printer Gateway ANN-S/PG.
– Optional LED Annunciator Driver ANN-I/O.
• Optional 4XTMF module (conventional reverse polarity/city
box transmitter).
PROGRAMMING AND SOFTWARE:
• Can be programmed at the panel with no special software
or additional equipment.
• Programmable Make/Break Ratio.
• Upload/Download (local or remote) of program and data via
integral DACT
Photoelectric Smoke Detectors
System Sensor i3™ series smoke detectors represent significant advancement in conventional detection.
The i3 family is founded on three principles: installation ease, intelligence, and instant inspection.
Features
• Plug-in detector line, mounting base included
• Large wire entry port
• In-line terminals with SEMS screws
• Mounts to octagonal and single-gang back boxes, 4-square back
boxes, or direct to ceiling
• Stop-Drop ’N Lock attachment to base
• Removable detector cover and chamber
• Built-in remote maintenance signaling
• Drift compensation and smoothing algorithms
• Simplified sensitivity measurement
• Wide-angle, dual-color LED indication
• Loop testing via EZ Walk feature
• Built-in test switch
Instant inspection.
The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector’s
condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is
available on 2-wire i3 detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector.
Indoor Selectable-Output Strobes and Horn Strobes for Ceiling Applications
SpectrAlert® Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits.
Features
• Plug-in design with minimal intrusion into the back box
• Tamper-resistant construction
• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela
• Field-selectable candela settings on ceiling units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and three volume selections
• Universal mounting plate for ceiling units
• Mounting plate shorting spring checks wiring continuity before device installation
• Electrically Compatible with legacy SpectrAlert devices
• Compatible with MDL sync module
• Listed for ceiling or wall mounting
The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry. With white and red plastic housings, wall and ceiling mounting options, and plain and FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement.
Like the entire SpectrAlert Advance product line, ceiling-mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults.
To further simplify installation and protect devices from construction damage, SpectrAlert Advance utilizes a universal mounting plate with an onboard shorting spring, so installers can test wiring continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with three volume selections.
Fire-Lite BG12SL Single Action Pull w/Key Lock
Features
-
Aesthetically pleasing, highly visible design/color.
-
Attractive contoured shape with light textured finish.
-
Meets ADA 5 lb. maximum pull-force.
-
Meets UL 38, Standard for Manually Actuated Signaling Boxes.
-
Easily operated (single- or dual-action), yet designed to prevent false alarms when bumped, shaken, or jarred.
-
PUSH IN/PULL DOWN handle latches in the down position to clearly indicate the station has been operated.
-
The word “ACTIVATED” appears on the top of the handle in bright yellow, further indicating operation of the station.
-
Operation handle features white arrows showing basic operation direction, for non-English-speaking persons.
-
Braille text included in finger-hold area of operation handle and across top of handle.
-
Multiple hex- and key-lock models available.
-
U.S. patent-pending hex-lock needs only a quarter-turn to lock/unlock.
-
Station can be opened for inspection and maintenance without initiating an alarm.
-
Product ID label viewable by simply opening the cover; label is made of a durable long-life material.
-
The words “NORMAL” and "ACTIVATED" are molded into the plastic adjacent to the alarm switch (located inside).
-
Four-position terminal strip molded into backplate.
-
Terminal strip includes Phillips combination-head captive 8/32 screws for easy connection to Initiating Device Circuit (IDC).
-
Terminal screws backed-out at factory and shipped ready to accept field wiring (up to 12 AWG/3.25 mm²).
-
Terminal numbers are molded into the backplate, eliminating the need for labels.
-
Switch contacts are normally open.
-
Can be surface (with SB-I/0 or SB-10) or semi-flush mounted. Semi-flush mount to a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box.
-
Backplate is large enough to overlap a single-gang backbox cutout by up to 1/2" (12.7 mm).
-
Optional trim ring (BG-TR).
-
Spanish version (FUEGO) available (BG-12LSP).
-
Designed to replace the Fire-Lite Legacy BG-10 Series.
-
Models packaged in attractive, clear plastic (PVC), clamshell-style, Point-of-Purchase packages. Packaging includes a cutaway dust/paint cover in shape of pull station.
Description
The Fire-Lite Alarms BG-12 Series is a cost-effective, feature-packed, non-coded series of manual fire alarm pullstations. It was designed to meet multiple applicationswith the installer and end-user in mind. The BG-12 Seriesfeatures a variety of models including single- and dualactionversions.The BG-12 Series provides Fire-Lite Fire Alarm ControlPanels (FACPs), as well as other manufacturers controls,with a manual alarm initiating input signal. Its innovativedesign, durable construction, and multiple mounting optionsmake the BG-12 Series simple to install, maintain,and operate.